Xantrex 865-1010 XW4024-120/240-60, 4000W, 24VDC XW Series Hybrid Inverter/Charger
XW4024-120/240-60, 4000W, 24VDC XW Series Hybrid Inverter/Charger
Xantrex brings the next generation of inverter/charger to market, with the XW Hybrid Inverter/Charger, the heart of the XW System. The XW Hybrid Inverter/Charger (XW) is a true sine wave, 120/240-volt AC, split-phase, inverter/charger that incorporates a DC to AC inverter, a battery charger, and an AC auto-transfer switch. It is the foundation for battery- based residential and commercial applications up to 18 kilowatts (kW). Capable of being grid-interactive or grid-independent, the XW can operate with generators and renewable energy sources to provide full time or backup power.
Description
Designed with consultation and input from industry experts, dealers, and installers, the XW sets a new standard for battery-based inverter/chargers. Integrating the best features available in the market, innovative new features by Xantrex and balance-of-systems components, the XW Hybrid Inverter/Charger's design makes installation quicker and easier. The XW offers high efficiency and unprecedented surge capacity to maximize the owner's return on investment. No other inverter/charger looks or performs like the XW.
Features of the Xantrex 865-1010 XW4024-120/240-60, 4000W, 24VDC XW Series Hybrid Inverter/Charger
Optional Accessories
Electrical Specifications | Model XW4024-120/240-60 |
Continuous output power: | 4000 Watts |
Surge rating (10 seconds): | 8000 Watts |
Surge current: | L-N: 70 Arms (20 sec) L-L: 35 Arms (20 sec) |
Waveform: | True sine wave |
Low-load efficiency: | 95% |
Idle consumption - search mode | < 8 Watts |
AC connections: | AC1 (Grid), AC2 (Generator) |
AC voltage: | 120/240 Vac split-phase |
AC input breaker: | 60 A two-pole |
Utility interactive: | yes |
CEC weighted efficiency: | 91% |
CEC power rating: | 4000 watts |
AC input voltage range (bypass/charge mode) | L-N: 80-150 Vac (120 V nominal); L-L: 160-270 Vac (240 V nominal) |
AC input frequency range (bypass/charge mode) | 55-65 Hz (default); 44-70 Hz (allowable) |
AC1 voltage range – Sell mode (automatically adjusts when entering Sell mode)* | L-N: 108-130 +/- 1.5 Vac; L-L: 214 - 260 +/- 3.0 Vac |
AC1 frequency range –Sell mode (automatically adjusts when entering Sell mode)* | 59.4 - 60.4 +/- 0.05 Hz |
AC output voltage: | L-N: 120 Vac +/- 3%; L-L: 240 Vac +/- 3% |
AC output frequency: | 60.0 +/-0.1 Hz |
DC current at rated power: | 178 Amps |
Total harmonic distortion: | < 5% |
Automatic transfer relay: | 60 Amps |
Typical transfer time: | 8 ms |
DC input voltage (nominal): | 25.2 Vdc |
DC input voltage range: | 22 - 32 Vdc |
Maximum continuous charge rate: | 150 Amps |
Efficiency at maximum charge rate: | 85.8% |
Power factor corrected charging: | 0.98 |
Emissions: | FCC Class B |
Multiple-unit configurations: | Up to three parallel units in 120/240-volt split- phase configuration |
Auxiliary relay output: | 0-12 Vdc, maximum 250 mA DC |
Non-volatile memory | Yes |
System network | Xanbus™ (publish-subscribe network, no need for hubs or special cards) |
Mechanical Specifications | |
Mounting: | Wall mount, backplate included |
Inverter dimensions (H x W x D) | 23 x 16 x 9” (580 x 410 x 230 mm) |
Inverter weight: | 116 lb (52.5 kg) |
Shipping weight: | 163 lb (74 kg) |
Display panel: | Status LEDs indicate AC In status, faults/warnings, equalize mode, battery level. Three-character display indicates output power or charge current, fault/warning codes. On/Off and equalize buttons |
Battery temperature sensor: | Included |
Standard warranty: | Five years (10 years optional) |
Part number: | 865-1000 |
Environmental Specifications | |
Enclosure type | NEMA Type 1 – Indoor (sensitive electronic components sealed inside enclosure) |
Operational temperature range: | -13°F to 158°F (-25°C to 70°C) |
Accessories | |
Remote display | Optional XW System Control Panel monitors and configures all devices connected to Xanbus™ Network |
Generator support: | Optional XW Automatic Generator Start module connects to Xanbus™ Network. Automatically activates generator to recharge depleted battery bank or assist inverter with heavy loads |
Power distribution & panel conduit boxes: | Optional balance-of-systems components for NEC compliant installations, includes pre-wired AC and DC circuit breakers, bus barsand multiple knockouts for conduit and additional breakers |
Regulatory Approval | UL 1741 1st Edition: 2005 Version CSA 107.1-01 |