SMA SB 10000TLUS-12 Sunny Boy 10000W Grid Tie Inverter with DC Disconnect
SB 10000TLUS-12 Sunny Boy 10000W Grid Tie Inverter with DC disconnect
Transformerless design. Maximum yields.
The new Sunny Boy TL-US series is UL-listed for North America and features SMA’s innovative H5 topology, resulting in superior efficiencies of up to 98 percent and unmatched solar yields. The transformerless design reduces weight, increases the speed of payback and provides optimum value for any decentralized, commercial PV system. The Sunny Boy TL-US series for North America is the ideal choice for mid-size and large plants from 24 kWp up to the megawatt ran.
Features of the SMA SB 10000TLUS-12 Sunny Boy 10000W Grid Tie Inverter with DC Disconnect:
Innovative
High-yield
Reliable
Convenient:
Also Known As:
SB.10000TLUS-12
SB-10000TLUS-12
SB_10000TLUS-12
SB10000TLUS-12
Also Known As:
SB.10000TLUS-12
SB-10000TLUS-12
SB_10000TLUS-12
SB10000TLUS-12
Sunny Boy 10000TL-US | Sunny Boy 10000TL-US | Sunny Boy 11000TL-US | |
208 V | 240 V | 240 V | |
Input (DC) | |||
Max. usable DC power | 10500 W | 10400 W | 11500 W |
Max. input voltage | 600 V | 600 V | 600 V |
MPP voltage range / rated input voltage | 300 V — 480 V / 345 V | 345 V — 480 V / 379 V | 345 V — 480 V / 379 V |
Min. input voltage / Initial input voltage | 300 V / 360 V | 345 V / 360 V | 345 V / 360 V |
Max. input current / Max. input per string | 35 A / 35 A | 30.2 A / 30.2 A | 33.3 A / 33.3 A |
Number of MPP trackers / fuse-protected strings per MPP tracker | 1 / 6 (@ Combiner Box) | 1 / 6 (@ Combiner Box) | 1 / 6 (@ Combiner Box) |
Output (AC) | |||
Rated power / max. apparent AC power | 10000 W | 10000 W | 11000 W |
Nominal AC voltage | 208 V | 240 V | 240 V |
Nominal AC voltage range | 183 V — 229 V | 211 V — 264 V | 211 V — 264 V |
AC power frequency; range | 60 Hz / 59.3 — 60.5 Hz | 60 Hz / 59.3 — 60.5 Hz | 60 Hz / 59.3 — 60.5 Hz |
Max. output current | 48.1 A | 41.7 A | 45.8 A |
Power factor at rated power | 1 | 1 | 1 |
Phase conductors / connection phases | 1 / 2 | 1 / 2 | 1 / 2 |
Efficiency | |||
CEC eficiency/ Max. efficiency | 98.0 % / 98.6 % | 98% / 98.7 % | 98% / 98.7 % |
Protection devices | |||
DC reverse-polarity protection | yes | yes | yes |
AC short circuit protection | yes | yes | yes |
Galvanically isolated / all-pole sensitive monitoring unit | —/ yes | —/ yes | —/ yes |
Arc-fault circuit interrupter | yes | yes | yes |
Protection class / overvoltage category | I / III | I / III | I / III |
General data | |||
Dimensions (W / H / D) in mm (in) | 470 / 615 / 240 (18.4 / 24.1 / 9.5) | ||
DC Disconnect dimensions (W / H/ D) in mm (in) | 187 / 297 / 190 (7.28 / 11.7 / 7.5) | ||
Weight / DC Disconnect weight | approx. 35 kg (78 lb) / 3.5 kg (8 lb) | ||
Operating temperature range (full power) | —40 °C ... +60 °C / —40 °F ... +140 °F | ||
Internal consumption: (night)) | ≤ 0.25 W | ≤ 0.25 W | ≤ 0.25 W |
Topology | Transformerless H5 | ||
Cooling concept | OptiCool | ||
Electronics protection rating / connection area | NEMA 3R / NEMA 3R | ||
Max. permissible value for relative humidity | 100% | ||
Features | |||
DC connection | Screw terminal | ||
AC connection | Screw terminal | ||
Display | Text line | ||
Interfaces: RS485 / Bluetooth | opt. / opt. | opt. / opt. | opt. / opt. |
Warranty: 10 / 15 / 20 years | yes / opt. / opt. | yes / opt. / opt. | yes / opt. / opt. |
Certificates and permits (more available on request) | UL1741, UL1998, IEEE 1547, FCC Part 15 (Class A & B), CSA C22.2 No. 107.1-2001 | UL1741, UL1998, IEEE 1547, FCC Part 15 (Class A & B), CSA C22.2 No. 107.1-2001 | UL1741, UL1998, IEEE 1547, FCC Part 15 (Class A & B), CSA C22.2 No. 107.1-2001 |
Type designation | SB 10000TLUS-12 | SB 11000TLUS-12 |