Schneider Electric 865-1060 XW AGS Automatic Generator Start
The XW Automatic Generator Start (XW AGS) will automatically activate a generator to provide an XW Series Hybrid Inverter/Charger with power to recharge a depleted battery bank or provide additional power for heavy loads. The XW AGS adds intelligence to generator management, thereby eliminating time spent monitoring batteries and inverter loads. It does this by continuously monitoring the battery voltage, state-of-charge, or the inverter charge mode, starting and stopping the generator when the battery needs additional charging. The XW AGS will also start the generator to assist the system's inverter/charger(s) when output power demands are high. The XW AGS can be customized to suit each user's preferences. The user can define whether the generator should be activated by low-battery voltage, state-of-charge, thermostat operation, or load on the inverter(s). A quiet time setting prevents the generator from starting at inconvenient times. LED lights display the status of the XW AGS, while all user-defined settings are programmed through the XW System Control Panel (XW SCP).
Operational Features
Product Features
Interfaces with:
Electrical Specifications | |
Nominal input network voltage | 15 Vdc |
Maximum operating current | 200 mA |
Communication | Physical layer 2, CAN |
Relay contact voltage rating | 12 Vdc, 30 Vdc max |
Maximum relay contact current | 5 Adc |
Communication protocol | Xanbus |
Maximum cable length | 130' (40 m) |
Mechanical Specifications | |
Dimensions (H x W x D) | 3.75 x 5.75 x 1.5" (95.5 x 146 x 37 mm) |
Weight (Controller only) | 0.5 lb (0.225 kg) |
Weight (shipping) | 1.70 lb (0.77 kg) |
Shipping dimensions (H x W x D) | 10.5 x 8.5 x 2.5" (267 x 216 x 64 mm) |
Connectors | Two Xanbus™ RJ45-8 pins One 20-contact pluggable connector (Tyco Mate 'n' Lok two connector |
Mounting | Wall mount, 4 x #6 screws included |
Standard warranty | Five years |
Part number | 865-1060 |
Environmental Specifications | |
Enclosure type | Indoor |
Operating temperature range (full power) | -4 to 122°F (-20 to 50°C) |
Storage temperature | -40 to 185 °F (-40 to +85 °C) |
Optional Accessories | |
Network cables: | |
3 feet (0.9 m) | 809-0935 |
25 feet (7.6 m) | 809-0940 |
50 feet (15.2 m) | 809-0941 |
75 feet (22.9 m) | 809-0942 |
Regulatory Approvals | |
CSA certified to CSA 107.1, and UL 458, FCC Class B and Industry Canada, CE Specifications subject to change without notice. |
No Longer Available
See Price at Checkout
See Price at Checkout