OutBack Power FXR2524A 2500W Hybrid Sealed Inverter/Charger
FXR2524A FXR Series Inverter/Charger
The latest, most advanced features on the industry’s most trusted and proven platform—that’s the essence of OutBack’s new FXR Series of Grid/Hybrid inverter/chargers. Capable of off-grid or grid-connected operation in a single model, the FXR Grid/Hybrid inverter/chargers provide system designers with unprecedented flexibility and compatibility for nearly
any power conversion scenario.
The new FXR features and technologies on the acclaimed
FX platform include:
Both off-grid and grid-tied functionality in one unit
FXR inverter/chargers can be paired with a MATE3 to add OPTICS RE to monitor and control system performance from any location. Available in power ranges from 2000W-3600W, multiple units may be stacked and connected with other OutBack Power electronics for more seamless system integration and the ability to function in a wide variety of applications, and system sizes. Up to nine inverters can be combined in a 3-phase system with the 12V, 24V or 48V models, and up to 36kW in a grid-tied 24V or 48V system. The exclusive modular system architecture means that increased power output is just an additional FXR inverter/charger away.
Available in sealed or vented units with NEMA type 1 die-cast aluminum chassis designed to operate in the harshest environmental conditions such as high temperatures, humidity or corrosive salt air, the FXR’s continue in OutBack’s tradition of absolute dependability in mission critical installations no matter how harsh or challenging the conditions.
Features of the OutBack Power FXR2524A 2500W Hybrid Sealed Inverter/Charger
Sealed Models | Vented Models | |||||||
FXR2012A | FXR2524A | FXR3048A | VFXR2812A | VFXR3524A | VFXR3648A | |||
Nominal DC Input Voltage | 12VDC | 24VDC | 48VDC | 12VDC | 24VDC | 48VDC | ||
Continuous Power Rating 25° C | 2000VA | 2500VA | 3000VA | 2800VA | 3500VA | 3600VA | ||
AC Output Frequency | 60Hz (50Hz) | 60Hz (50Hz) | ||||||
AC Output Voltage | 120VAC (100-130VAC) | 120VAC (100-130VAC) | ||||||
Continuous AC RMS Output @ 25° C | 16.7AAC | 20.8AAC | 25AAC | 23.3AAC | 29.2AAC | 30AAC | ||
Idle Power | Full: 34W Search: 9W Off: 3W | Full: 34W Search: 9W Off: 3W | ||||||
Typical Efficiency | 90% | 92% | 93% | 90% | 92% | 93% | ||
Total Harmonic Distortion | Typical | 2% | 2% | |||||
Maximum | 5% | 5% | ||||||
Output Voltage Regulation | +/- 2.5% | +/- 2.5% | ||||||
Maximum Output Current | Peak | 56AAC | 70AAC | 70AAC | 56AAC | 70AAC | 70AAC | |
RMS | 40AAC | 50AAC | 50AAC | 40AAC | 50AAC | 50AAC | ||
AC Overload Capablility | Surge | 4800VA | 6000VA | 6000VA | 4800VA | 6000VA | 6000VA | |
5 sec | 4500VA | 5400VA | 5400VA | 4500VA | 5400VA | 5400VA | ||
30 min | 2500VA | 3200VA | 3200VA | 3200VA | 4000VA | 4000VA | ||
AC Input Voltage Range (MATE Adjustable) | 85 to 140 VAC | 85 to 140 VAC | ||||||
AC Input Tare Loss | 54 to 66 Hz | 54 to 66 Hz | ||||||
Grid-Interactive Volatge Range | -- | 106 to 132VAC | 106 to 132VAC | -- | 106 to 132VAC | 106 to 132VAC | ||
Grid-Interactive Frequency Range | -- | 59.3 to 60.5 Hz | 59.3 to 60.5 Hz | -- | 59.3 to 60.5 Hz | 59.3 to 60.5 Hz | ||
AC Input Currrent Maximum | 60AAC | 60AAC | ||||||
Continuous Battery Charge Option | 100ADC | 55ADC | 35ADC | 125ADC | 82ADC | 45ADC | ||
Maximum Batter Charging (AC/DC/Power) | 14ACC / 100ADC / 1360VA | 14ACC / 55ADC / 1500VA | 14ACC / 35ADC / 1900VA | 18ACC / 125ADC / 1700VA | 20ACC / 82ADC / 2230VA | 20ACC / 45ADC / 2450VA | ||
DC Input Volatage Range | 10.5 to 17VDC | 21 to 34VDC | 42 to 68VDC | 10.5 to 17VDC | 21 to 34VDC | 42 to 68VDC | ||
Warranty | Standard 5 year / Optional 10 year | Standard 5 year / Optional 10 year | ||||||
Weight | Unit | 62 bs (29 kg) | 61 lbs (28 kg) | |||||
Shipping | 67 lbs (30 kg) | 67 lbs (30 kg) | ||||||
Dimensions | Unit | 13 x 8.25 x 16.25” (33 x 21 x 41 cm) | 12 x 8.25 x 16.25” (30 x 21 x 41 cm) | |||||
Shipping | 21.75 x 13 x 22” (55 x 33 x 56 cm) | 21.75 x 13 x 22" (55 x 33 x 56 cm) | ||||||
Ralative Humidity rating | 93% | 93% | ||||||
Listing/Certifications | UL 1741, CSA C22.2 No. 107.1, UL 1778 Annex FF | UL 1741, CSA C22.2 No. 107.1, UL 1778 Annex FF | ||||||
RoHS Complaince | Yes | Yes |