Citel DS210-48DC Surge Protector 48 Vdc
DS210-48DC Surge Protector - 48 Vdc
DS210-xxDC is a DC Surge Protection Device (SPD) for remote, off grid DC power applications. The DS210-xxDC provides protection against the direct and indirect effects of lightning. The DS210-xxDC is a dual pole module protecting both positive and negative to ground and is available for DC power system voltages of 12, 24, 48, 75, 95, 110 and 130 Vdc. It is installed in-line or parallel with the power system and is mounted on a din rail for application directly next to the charge controller or power supply.
The DS210-xxDC incorporates a proven Metal Oxide Varistor (MOV) protection circuit and specific DC thermal fuses that allow robust surge current handling up to 6kA 8/20us and reliable DC disconnection. These units have visual fault indicators and replaceable protection modules.
Also Known As:
DS210.48DC
DS210 48DC
DS210_48DC
DS21048DC
CITEL Part Number | DS210-12DC | DS210-24DC | DS210-48DC | DS210-75DC | DS210-95DC | DS210-110DC | DS210-130DC |
Nominal DC Voltage - Un-dc | 12 Vdc | 24 Vdc | 48 Vdc | 75 Vdc | 95 Vdc | 110 Vdc | 130 Vdc |
Maximal AC Voltage - Uc | 10 Vac | 15 Vac | 40 Vac | 60 Vac | 75 Vac | 95 Vac | 115 Vac |
Maximal DC Voltage - Uc-dc | 15 Vdc | 30 Vdc | 56 Vdc | 85 Vdc | 100 Vdc | 125 Vdc | 150 Vdc |
Nominal Discharge Current ln | 1 kA | 1 kA | 1 kA | 2 kA | 2 kA | 2 kA | 2 kA |
Maximum Discharge Current lmax | |||||||
Protection Level (at In) - Up | 85 V | 105 V | 180 V | 250 V | 300 V | 350 V | 400 V |
Thermal Disconnector | Internal | ||||||
Fuses | Fuses - 50 A time delay see diagram | ||||||
Dimensions | See Diagram | ||||||
Connection | By screw terminals : #8 AWG MAX | ||||||
Disconnection Indicator | Green led off | ||||||
Mounting | Symmetrical Rail 35 mm | ||||||
Operating Temperature | -40/+85 °C | ||||||
Protection Class | IP20 | ||||||
Housing Material | Thermoplastic UL94-V0 |