| | PVI-12.0-I-OUTD-US-480 |
| Input Side | |
| Start-up Input Voltage (Vdcstart) | adj. 120...350 V |
| Operating Input Range (Vdcmin...Vdcmax) | 0.7 x Vdcstart...520 V |
| MPP Input range (Vmppmaxf-Vmppmin,f) at full power | 250...470 V |
| Input Voltage Range for Full Power Operation with Parallel Configuration of MPPT | 250...470 V |
| Input Voltage Range for Full Power Operation with Independent Configuration of MPPT | 260...470 V (@6,500W) / 240...470 V (@5,800W) |
| Absolute Maximum Input Voltage Vmax,abs | 520 V |
| Number of Independent MPPT | 2 |
| Maximum Input Current (Idcmax) | 25.0 A |
| Number of DC Inputs Pairs | 2 (3 on -S2 version) for each MPPT |
| Input Protection | |
| Reverse Polarity protection | Yes |
| Input Short Circuit Current | 29.0 A |
| Input Side Varistors | 4 (2 for each MPPT) |
| Photovoltaic Array Isolation Control | GFDI |
| DC Switch | 600 V /32 A |
| Output Side | |
| AC Grid Connection (Vacmin...V acmax) | Three Phases |
| Rated Power (Pac,r) | 12,000 W |
| Power at 50°C/122°F | 11,160 W |
| Power at 60°C/140°F | 8,950 W |
| Rated Grid Voltage (Vac,r) | 480 Vac |
| AC Voltage Range | 422...528 V |
| Maximum Output Current (Iac,max) | 16.0 A |
| Rated Frequency (fr) | 60 Hz |
| Nominal Power Factor | > 0.99 |
| Total Harmonic Distortion | < 2% |
| Output Protection | |
| Anti-islanding protection | According to UL 1741 |
| Maximum AC Overcurrent Protection | 20.0 A |
| AC Side Varistors | 3 plus gas arrester |
| Night Time Disconnect | Yes |
| Operating Performance | |
| Maximum Efficiency (ηmax) | 97.30% |
| Weighted Effi ciency (EURO/CEC) | - / 97.0 % |
| Feed In Power Threshold | 30 W |
| Stand-by Consumption | < 8 W |
| Night-time power loss | < 0.3 W |
| Communication | |
| Monitoring System (PC/Data logger) | RS485/232 (opt.), Aurora Desktop (opt.) |
| Remote Control | RS 485, Wireless (opt.) |
| User Interface | 16 characters x 2 lines LCD display |
| Environmental | |
| Ambient Temperature Range | -25...+60°C /-13...140°F with derating above 45°C/113°F |
| Relative Humidity | < 100 % condensing |
| Noise Emission | < 50 db(A) |
| Operating Altitude | 2000 m / 6560 ft |
| Physical | |
| Environmental Protection Rating | NEMA 4X |
| Cooling | Natural |
| Dimension (H x W x D) | 716mm x 645mm x 208mm / 28.2” x 25.4” x 8.2” 958 mm x 645mm x 222m / 37.7”x12.8”x8.7” (-S/-S2) |
| Weight | 45.8 kg / 99.0 lb 48.5 kg / 107 lb (-S Version) 51.7 / 114 lb (-S2 Version) |
| Mounting System | Bracket support |
| Warranty | 10 std up to 15/20 years opt. |
| Safety | |
| Isolation Level | HF transformer |
| Marking | cCSAus |
| Safety and EMC Standard | UL 1741, CSA - C22.2 N. 107.1-01 |
| Grid Standard | IEEE 1547 |
| Available Products Variants | |
| Standard - Positive Ground | PVI-12.0-I-OUTD-US-480-PG |
| Standard - Negative Ground | PVI-12.0-I-OUTD-US-480-NG |
| With DC Switch - Positive Ground | PVI-12.0-I-OUTD-S-US-480-PG |
| With DC Switch - Negative Ground | PVI-12.0-I-OUTD-S-US-480-NG |
| With AC and DC Switches - Positive Ground | PVI-12.0-I-OUTD-S2-US-480-PG |
| With AC and DC Switches - Negative Ground | PVI-12.0-I-OUTD-S2-US-480-NG |