Aurora Inverters utilize high-efficiency power-conversion technologies, and high-speed independent Maximum Power Point Tracking (MPPT) channels, to increase the amount of usable power that is available from renewable-energy installations. This optimized energy harvesting can significantly increase the ROI of residential and commercial solar-power plants. Aurora PVI-Series Inverters deliver optimized energy harvesting across a broad range of photovoltaic applications and operating conditions. Outdoor products feature rugged IP65 (NEMA 4X) rated enclosures. Indoor products combine attractive space-saving packaging with industry-leading performance and features.
Also Known As:
PVI.3.6.OUTD.US
PVI 3.6 OUTD US
PVI_3.6_OUTD_US
PVI3.6OUTDUS
PVI-3.0-OUTD/-S | PVI-3.6-OUTD/-S | PVI-4.2-OUTD/-S | ||
INPUT PARAMETERS (DC Side) | ||||
Nominal DC Power | 3120 W | 3750 W | 4380 W | |
Total Max DC Power | 3500 W | 4150 W | 4820 W | |
Operating MPPT Input Voltage Range | 90 V to 580 V (360Vnominal) | |||
Full Power MPPT Range | 160 V to 530 V | 200 V to 530 V @ Vgrid 277 V 200 V to 530 V @ Vgrid 240 V 220 V to 530 V @ Vgrid 208 V | 200 V to 530 V @ Vgrid 277 V 200 V to 530 V @ Vgrid 240 V 220 V to 530 V @ Vgrid 208 V | |
Max Input Voltage | 600 V | |||
Activation Voltage | 200 V nominal (adjustable from 120 V to 350 V) | |||
Number of Independent MPPT Channels | 2 | |||
Max DC Power On Each MPPT Channel | 2000 W | 3000 W | 3000 W | |
Max. DC Current Per MPPT Channel | 10A (12.5A short circuit) | 16A (20A short circuit) | 16A (20A short circuit) | |
Thermal Protected DC Side Varistor | 4 | |||
DC Switch | Integrated in the -S versions (rating 600V/25A) | |||
DC Connections | 4 (2 positive; 2 negative) Screw Terminal Block Wire sizes : Solid, from, AWG20 to AWG 6 - Stranded, from AWG20 to AWG 9 Cable Gland: M25 - Cable diameter: 3/8" to 11/16" | |||
OUTPUT PARAMETERS (AC Side) | ||||
Nominal AC Power | 3000 W | 3600 W | 4200 W | |
Max AC Power | 3300 W | 4000 W | 4600 W | |
AC Grid Connection | split phase 240V -single phase 208V/277V | |||
Nominal AC Voltage | Default 240V - Optional 208V or 277V (setting required) | |||
AC Voltage Range | 277 V (244-304) 240 V (211-264) 208 V (183-228) | |||
Nominal AC Frequency | 60 Hz | |||
Continous AC Output Current | 12A -14.5A -14.5A | 16A -17.2A -17.2A | 20A -20A -20A | |
Maximum Output OC Protection | 15A -20A -20A | 15A -25A -25A | 25A -25A -25A | |
AC Side Varistor | 2 (live-netrual / live-PE) | |||
AC Connection | Screw Terminal Block Wire sizes : Solid, from, AWG20 to AWG 6 - Stranded, from AWG20 to AWG 8 Cable Gland: M25 - Cable diameter: 3/8" to 11/16" | |||
Line Power Factor | 1 | |||
AC Current Distrortion | < 2% at rated power with sine wave voltage | |||
Max Effi ciency | 96.8% | |||
CEC Effi ciency | 96% | |||
Feed in Power Threshold | 20W | |||
Night Time Consumption | <2W | |||
Isolation | Non-Isolated Transformerless Topology | |||
ENVIRONMENTAL PARAMETERS | ||||
Cooling | Natural cooling | |||
Ambient Temp. Range [°C] | -25°C to +60°C output power derating for Tamb > 55°C | -25°C to +60°C derating for Tamb > 45°C | ||
Operating Altitude | 6,000 ft | |||
Acustical Noise | < 50 dBA @ 1mt | |||
Environmental NEMA Rating | NEMA 4X | |||
Relative Humidity | 0-100% condensing | |||
MECHANICAL | ||||
Dimensions (HxWxD) [inches] | -S version : 787x352x208mm -(31", 12 3/4", 8 1/4") basic version : 547x352x208mm -(21 1/2", 12 3/4", 8 1/4") | |||
Weight | 17 Kg (37.5 lbs) -21Kg (46.25 lbs) | |||
OTHER | ||||
Display | Two Line Alphanumeric LCD | |||
Communication | RS485 (spring terminal block - wire cross section: AWG28-16) USB connection (for Service only) AURORA® Easy Control system for remote control (Optional) |